List of parameters
Parameters
1-859
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Values: 0: No sensor available
10: PTC fault
11: PTC alarm
12: PTC alarm and timer stage
20: KTY84
30: Bimetallic NC contact fault
31: Bimetallic NC contact alarm
32: Bimetallic NC contact alarm and timer stage
Dependency: Refer to: r0458, p0600, p0601
Note: Terminals for PTC triplet: X200.5, X200.6
PTC thermistor: Tripping resistance = 1650 Ohm
Description: Displays the actual temperatures in the motor, measured via an SME 120 or SME 125.
Index: [0] = SME temperature channel 1
[1] = SME temperature channel 2
[2] = SME temperature channel 3
[3] = SME temperature channel 4
Note: An invalid temperature is displayed using the value -200°C.
Description: Sets the component number for the Sensor Module Integrated (SMI) for which data should be saved or down-
loaded.
Dependency: Refer to: p4691, p4692
Note: SMI: SINAMICS Sensor Module Integrated
Only component numbers that correspond to a Sensor Module Integrated can be entered.
Description: Setting to save/download the data for the Sensor Module Integrated (SMI) specified in p4690.
Procedure:
p4690 = set component number
p4691 = 1, 2 set the required procedure (save/download)
p4691 = 0 --> automatically after the procedure has been successfully completed
p4691 = 11, 12, 13, 14, 15 --> error vales if the procedure was not able to be executed
r4620[0...3] Motor temperatures SME / Mot Temp SME
SERVO, VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]
p4690 SMI component number / SMI comp_no
CU_CX32, CU_S Can be changed: T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 399 0
p4691 Save/download SMI data / Save/DL SMI data
CU_CX32, CU_S Can be changed: T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 15 0