List of parameters
Parameters
1-795
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Index: [0] = AI 0 (X523.1/X523.2)
Note: AI: Analog Input
Description: Sets the smoothing time constant of the 1st-order low pass filter for the analog inputs of the Terminal Board 30
(TB30).
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note: AI: Analog Input
Description: Sets the smoothing time constant of the 1st-order low pass filter for the analog inputs of terminal module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note: AI: Analog Input
Description: Sets the smoothing time constant of the 1st-order low pass filter for the analog inputs of terminal module 41 (TM41).
Index: [0] = AI 0 (X523.1/X523.2)
Note: AI: Analog Input
Description: Displays the currently referred input value of the analog inputs of Terminal Board 30 (TB30).
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note: AI: Analog Input
p4053[0...1] TB30 analog inputs, smoothing time constant / TB30 AI T_smooth
TB30 Can be changed: U, T Calculated: - Access level: 1
Data type: Floating Point Dynamic index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 0.0 [ms]
p4053[0...1] TM31 analog inputs, smoothing time constant / TM31 AI T_smooth
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Floating Point Dynamic index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 0.0 [ms]
p4053[0...0] TM41 analog inputs, smoothing time constant / TM41 AI T_smooth
TM41 Can be changed: U, T Calculated: - Access level: 1
Data type: Floating Point Dynamic index: - Func. diagram: 9663
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 0.0 [ms]
r4055[0...1] CO: TB30 analog inputs, actual value in percent / TB30 AI value in %
TB30 Can be changed: - Calculated: - Access level: 1
Data type: Floating Point Dynamic index: - Func. diagram: 1790, 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]