A01485 Topology: Comparison CX32 missing in the actual topology
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected a controller extension 32 (CX32) in the target topology that is not available
in the actual topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Note:
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy: - delete the CX32 in the commissioning software project and download the new configuration into the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. set-
point/actual value comparison).
A01486 Topology: Comparison DRIVE-CLiQ components missing in the actual topology
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected a DRIVE-CLiQ component in the target topology that is not available in the
actual topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Note:
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy: - delete the drive belonging to this component in the commissioning software project and download the new config-
uration into the drive unit.
- re-configure the drive belonging to this component in the commissioning software project and download the new
configuration into the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. set-
point/actual value comparison).
A01487 Topology: Comparison option slot components missing in the actual topology
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected an option slot module in the target topology that is not available in the actual
topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Note:
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy: - delete the option board in the commissioning software project and download the new configuration into the drive
unit.
- re-configure the drive unit in the commissioning software project and download the new configuration into the drive
unit.
- check that the actual topology matches the target topology and if required, change over.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. set-
point/actual value comparison).