PROFIdrive
Function Diagrams
2-1181
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-73 2483 – IF1 send telegram, free interconnection via BICO (p0922 = 999)
- 2483 -
Function diagram
87654321
fp_2483_01_eng.vsd
DO: A_INF, B_INF, CU_S, S_INF, TB30, TM15DI_DO, TM31
SINAMICS S
29.06.07 V02.05.01
PROFIdrive - IF1 send telegram, free interconnection via BICO (p0922 = 999)
<1> In order to maintain the PROFIdrive profile, send word 1 must be used as status word 1 (E_ZSW1) for A_INF, B_INF and S_INF.
<2> Using the binector/connector converters at [2472], bits of 4 send words can be interconnected with any binectors.
<3> The following representation applies for words: 4000 hex = 100 %.
The reference variables p200x apply for the ongoing interconnection (100 % -> p200x).
The following applies for temperature values: 100 °C -> 100 % = 4000 hex; 0 °C -> 0 %.
<4> Valid for CU_S.
<5> Valid for A_INF, B_INF, S_INF.
Refer to [1020.7]
PROFIdrive Abtastzeit
<3>
<1>
PZD send word 7(0)
p2051[6]
<4>
PZD send word 8
PZD send word 13
PZD send word 14
PZD send word 15
<4>
<4>
<4>
<4>
<4>
<4>
(0)
p2051[7]
(0)
p2051[12]
(0)
p2051[13]
(0)
p2051[14]
<4>
<4>
<4>
<4>
<4>
<5>
<5>
<5>
<5>
<5>
PROFIBUS
PROFINET
Drive object n
Header
Drive object 1
Drive object 2
.
.
.
.
.
.
Drive object m
Trailer
IF1 Diag send word 1...7
r2053[0...6]
...
PZD send word 1
PZD send word 2
PZD send word 3
PZD send word 4
PZD send word 5
<2>
(0)
p2051[1]
(0)
p2051[2]
(0)
p2051[3]
(0)
p2051[4]
(0)
p2051[0]
PZD send word 6(0)
p2051[5]
PROFIdrive send telegram
Reference quantities for further interconnection
p200x
<4>
<5>