Parameters
List of parameters
1-272
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the send and receive telegram.
Values: 7: Standard telegram 7, PZD-2/2
9: Standard telegram 9, PZD-6/5
110: SIEMENS telegram 110, PZD-12/7
999: Free telegram configuration with BICO
Dependency: Refer to: p2038
Refer to: F01505, F01506
Note: For p0922 = 100 ... 199, p2038 is automatically set to 1 and p2038 can no longer be changed. This means that for
these telegrams, the "SIMODRIVE 611 universal" interface mode is set and cannot be changed.
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
Description: Sets the send and receive telegram.
Values: 1: Standard telegram 1, PZD-2/2
2: Standard telegram 2, PZD-4/4
20: Standard telegram 20, PZD-2/6
352: SIEMENS telegram 352, PZD-6/6
999: Free telegram configuration with BICO
Dependency: Refer to: F01505, F01506
Caution: Telegrams 2, 3 and 4 are not suitable for sensorless vector control (p1300 = 20). For sensorless vector control, it is
necessary that the setpoint speed is entered at the ramp-function generator input (e.g. p1070) and not after the
ramp-function generator (p1155).
Note: If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
Description: Sets the send and receive telegram.
p0922 PROFIdrive telegram selection / PD Telegr_sel
SERVO (EPOS) Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2420,
2422, 2423, 2460, 2470
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
7 999 999
p0922 PROFIdrive telegram selection / PD Telegr_sel
VECTOR Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2420,
2422, 2423, 2460, 2470
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1 999 999
p0922 PROFIdrive telegram selection / PD Telegr_sel
VECTOR (n/M) Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2420,
2422, 2423, 2460, 2470
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1 999 999