Siemens SINAMICS S Series - r3608 Infeed reactive current controller system deviation; INF I_reactvCtrDev; p3610 Infeed reactive current fixed setpoint; INF I_reactv F_set; p3611 CI: Infeed reactive current supplementary setpoint; INF I_reactv Z_set; p3614 Infeed current actual value filter smoothing time; INF I_act t_sm

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-720
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the system deviation of the reactive current controller.
Description: Sets the fixed setpoint for the reactive current.
Description: Sets the signal source for the supplementary setpoint of the reactive current.
Description: Sets the time constant for the PT1 filtering of the active current actual value and reactive current actual value.
Note: The PT1 filter with a clock cycle dead time can be used to stabilize the closed-loop current control for extremely
weak line supplies with higher relative short-circuit voltage uk).
The current actual value filter is de-activated with p3614 = 0.
For an automatic controller setting with p3410 >= 2, the current actual value filter is automatically preset.
Description: Sets the normalized P gain for closed-loop current control of the infeed.
Note: A value of 100 % corresponds to the basic setting derived from loop control parameters (p3421, p3422).
r3608 Infeed reactive current controller system deviation / INF I_reactvCtrDev
A_INF Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 8946
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p3610 Infeed reactive current fixed setpoint / INF I_reactv F_set
A_INF Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 1774, 8946
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
-10000.0 [Arms] 10000.0 [Arms] 0.0 [Arms]
p3611 CI: Infeed reactive current supplementary setpoint / INF I_reactv Z_set
A_INF Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dynamic index: - Func. diagram: 8946
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p3614 Infeed current actual value filter smoothing time / INF I_act t_sm
A_INF Can be changed: T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8950
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [ms] 2.000 [ms] 0.000 [ms]
p3615 Infeed current controller P gain / INF I_ctrl Kp
A_INF Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 8946
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 1000.00 [%] 100.00 [%]