List of parameters
Parameters
1-455
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the limited field-generating current setpoint (Id_set).
This value comprises the steady-state field-generating current setpoint r1623 and a dynamic component that is only
set when changes are made to the flux setpoint.
Description: Gain factor to weight the excitation current setpoint.
Description: Displays the calculated excitation current setpoint.
Dependency: Refer to: p0390
Description: Displays the load angle of the current model.
Description: Dynamic factor of the model controller in the current model
r1624 Field-generating current setpoint, total / Id_setp total
VECTOR (n/M) Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: 6640, 6723,
6724, 6727
P-Group: Displays, signals Units group: 6_2 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p1625[0...n] Excitation current setpoint calibration / I_exc_setp cal
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
10.0 [%] 200.0 [%] 100.0 [%]
r1626 CO: Excitation current setpoint / I_exc_setp
VECTOR (n/M) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 6727
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r1627 CO: Current model load angle / I_mod load angle
VECTOR (n/M) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 6727
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
- [°] - [°] - [°]
p1628[0...n] Current model controller, dynamic factor / I_mod_ctr dyn_fact
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6727
P-Group: Functions Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
1 [%] 400 [%] 50 [%]