Siemens SINAMICS S Series - r1087 Velocity limit negative effective; v_limit neg eff; p1088[0...n] CI: Speed limit negative direction of rotation; n_limit neg; p1088[0...n] CI: Velocity limit negative direction; n_limit neg; p1091[0...n] Skip speed 1; n_skip 1

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-314
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the effective negative velocity limit.
Dependency: Refer to: p1082, p1086, p1088
Description: Sets the signal source for the speed/velocity limit of the negative direction.
Description: Sets the signal source for the speed/velocity limit of the negative direction.
Description: Sets skip speed 1.
Dependency: Refer to: p1092, p1093, p1094, p1101
Note: The skip (suppression) speeds can be used to prevent the effects of mechanical resonance.
Description: Sets skip velocity 1.
Dependency: Refer to: p1092, p1093, p1094, p1101
Note: The skip (suppression) velocities can be used to prevent the effects of mechanical resonance.
r1087 Velocity limit negative effective / v_limit neg eff
SERVO (Lin) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 3050, 5030,
5210, 6640, 7020, 8010
P-Group: Setpoints Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [m/min] - [m/min] - [m/min]
p1088[0...n] CI: Speed limit negative direction of rotation / n_limit neg
SERVO (Extended
setp), VECTOR
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 3050
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1086[0]
p1088[0...n] CI: Velocity limit negative direction / n_limit neg
SERVO (Extended
setp, Lin)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 3050
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1086[0]
p1091[0...n] Skip speed 1 / n_skip 1
SERVO (Extended
setp), VECTOR
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [RPM] 210000.000 [RPM] 0.000 [RPM]
p1091[0...n] Skip velocity 1 / v_skip 1
SERVO (Extended
setp, Lin)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [m/min] 1000.000 [m/min] 0.000 [m/min]