Parameters
List of parameters
1-314
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the effective negative velocity limit.
Dependency: Refer to: p1082, p1086, p1088
Description: Sets the signal source for the speed/velocity limit of the negative direction.
Description: Sets the signal source for the speed/velocity limit of the negative direction.
Description: Sets skip speed 1.
Dependency: Refer to: p1092, p1093, p1094, p1101
Note: The skip (suppression) speeds can be used to prevent the effects of mechanical resonance.
Description: Sets skip velocity 1.
Dependency: Refer to: p1092, p1093, p1094, p1101
Note: The skip (suppression) velocities can be used to prevent the effects of mechanical resonance.
r1087 Velocity limit negative effective / v_limit neg eff
SERVO (Lin) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 3050, 5030,
5210, 6640, 7020, 8010
P-Group: Setpoints Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [m/min] - [m/min] - [m/min]
p1088[0...n] CI: Speed limit negative direction of rotation / n_limit neg
SERVO (Extended
setp), VECTOR
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 3050
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1086[0]
p1088[0...n] CI: Velocity limit negative direction / n_limit neg
SERVO (Extended
setp, Lin)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 3050
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1086[0]
p1091[0...n] Skip speed 1 / n_skip 1
SERVO (Extended
setp), VECTOR
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [RPM] 210000.000 [RPM] 0.000 [RPM]
p1091[0...n] Skip velocity 1 / v_skip 1
SERVO (Extended
setp, Lin)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [m/min] 1000.000 [m/min] 0.000 [m/min]