Siemens SINAMICS S Series - r1286 Vdc_min controller switch-in level (kinetic buffering) (V;f); Vdc_min on_level; p1287[0...n] Vdc_min controller dynamic factor (kinetic buffering) (V;f); Vdc_min dyn_factor; p1289[0...n] Vdc_max controller speed threshold (V;f); Vdc_max n_thresh; p1290[0...n] Vdc controller proportional gain (V;f); Vdc_ctrl Kp

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-366
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the switch-in level for the Vdc_min controller (kinetic buffering).
Description: Sets the dynamic factor for the Vdc-min controller (kinetic buffering).
100 % means that p1290, p1291 and p1292 (gain, integral time and rate time) are used corresponding to their basic
settings and based on a theoretical controller optimization.
If subsequent optimization is required, then this can be realized using the dynamic factor. In this case p1290,
p1291, p1292 are weighted with the dynamic factor p1287.
If several modules are connected to the DC link, then the dynamic factor must be increased corresponding to the
ratio of the additional capacitances to the capacitance of the module involved.
Note: The pre-setting of the dynamic factor is based on the power units connected at DRIVE-CLiQ. It is assumed that the
power unit, connected via DRIVE-CLiQ is also electrically connected to the DC link. If this is not the case, then the
dynamic factor must be optimized manually.
Description: Sets the lower speed threshold for the Vdc_max controller. When this speed threshold is fallen below, the Vdc_max
control is switched-out and the speed is controlled using the ramp-function generator.
Description: Sets the proportional gain for the Vdc controller (DC link voltage controller).
Note: The gain factor is proportional to the capacitance of the DC link. The parameter is preset to a value that is optimally
adapted to the capacitance of the individual Motor Module. The capacitances of the other power units, which are
connected to the DC link, can be taken into account using the dynamic factor (p1287 or p1283).
r1286 Vdc_min controller switch-in level (kinetic buffering) (V/f) / Vdc_min on_level
VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 6320
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
p1287[0...n] Vdc_min controller dynamic factor (kinetic buffering) (V/f) / Vdc_min dyn_factor
VECTOR Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1 [%] 10000 [%] 100 [%]
p1289[0...n] Vdc_max controller speed threshold (V/f) / Vdc_max n_thresh
VECTOR Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Functions Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [RPM] 210000.0 [RPM] 10.0 [RPM]
p1290[0...n] Vdc controller proportional gain (V/f) / Vdc_ctrl Kp
VECTOR Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6320
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 100.00 1.00