List of parameters
Parameters
1-239
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
This parameter is not saved when data is backed-up (p0971, p0977).
Description: Sets the setpoint for the input signals in the digital input simulation mode.
Description: Sets the sampling time for the inputs and outputs.
Dependency: The parameter can only be modified for p0009 = 3, 29.
The sampling times can only be set as an integer multiple of the basic sampling time (p0110, p0111).
Refer to: p0009, r0110, r0111
Note: The modified sampling time is not effective until the drive unit is powered-up again.
Description: Sets the sampling time for the inputs and outputs.
p0796 CX digital inputs, simulation mode, setpoint / CX DI simul setp
CU_CX32 Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 Dynamic index: - Func. diagram: 2020, 2030,
2031
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X122.1) High Low -
01 DI 1 (X122.2) High Low -
02 DI 2 (X122.3) High Low -
03 DI 3 (X122.4) High Low -
08 DI/DO 8 (X122.7) High Low -
09 DI/DO 9 (X122.8) High Low -
10 DI/DO 10 (X122.10) High Low -
11 DI/DO 11 (X122.11) High Low -
p0799 CU inputs/outputs, sampling time / CU I/O t_sampl
CU_S Can be changed: C1(3) Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 2020, 2030,
2031, 2120, 2121, 2130, 2131,
2132, 2133
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 5000.00 [µs] 4000.00 [µs]
p0799 CX inputs/outputs, sampling time / CX I/O t_sampl
CU_CX32 Can be changed: C1(3) Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 2220, 2230,
2231
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 5000.00 [µs] 4000.00 [µs]