Description: Sets the setpoint after the ramp-function generator of the technology controller.
Description: Sets the time constant for the setpoint filter (PT1) of the technology controller.
Description: Displays the smoothed setpoint after the setpoint filter (PT1) of the technology controller.
Description: Sets the technology controller type.
Values: 0: D component in the actual value signal
1: D component in the fault signal
Description: Sets the signal source for the actual value of the technology controller.
r2260 CO: Technology controller setpoint after ramp-function generator /
Tec_ctr set aftRFG
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p2261 Technology controller setpoint filter time constant / Tec_ctrl set T
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [s] 60.00 [s] 0.00 [s]
r2262 CO: Technology controller setpoint after filter / Tec_ctr set aftFlt
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p2263 Technology controller type / Tec_ctrl type
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1 0
p2264[0...n] CI: Technology controller actual value / Tec_ctrl act val
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0