List of parameters
Parameters
1-259
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note: OC: Operating condition
Description: Displays the control word of the sequence control.
Note: OC: Operating condition
Description: Displays the status word from drive object 1 (Control Unit).
Description: Displays the status word of the infeed sequence control.
07 Command open brake Yes No -
08 Jog 1 Yes No -
09 Jog 2 Yes No -
10 Master ctrl by PLC Yes No -
12 Velocity controller enable Yes No -
14 Command close brake Yes No -
r0898.0...13 CO/BO: Control word sequence control / STW seq_ctrl
TM41 Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 9678
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Enable operation Yes No -
04 Enables the ramp-function generator Yes No -
05 Start ramp-function generator Yes No -
06 Enable speed setpoint Yes No -
07 Acknowledge fault Yes No -
13 Enable zero mark Yes No -
r0899.3...15 CO/BO: Status word drive object 1 / ZSW DO1
CU_CX32, CU_S Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
03 Fault present Yes No -
07 Alarm present Yes No -
08 System time synchronized Yes No -
12 Slave sign-of-life bit 0 Yes No -
13 Slave sign-of-life bit 1 Yes No -
14 Slave sign-of-life bit 2 Yes No -
15 Slave sign-of-life bit 3 Yes No -
r0899.0...12 CO/BO: Status word sequence control infeed / ZSW seq_ctrl INF
A_INF, S_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 8826,
8926
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -