Overview of parameters
Parameters
1-19
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Calculated
Specifies whether the parameter is influenced by automatic calculations.
The calculation attribute defines which activities influence the parameter.
The following attributes apply:
• CALC_MOD_ALL
− p0340 = 1
− Project download with commissioning software and send from p0340 = 3
• CALC_MOD_CON
− p0340 = 1, 4
• CALC_MOD_EQU
− p0340 = 1, 2
• CALC_MOD_LIM_REF
− p0340 = 1, 3, 5
− p0578 = 1
• CALC_MOD_REG
− p0340 = 1, 3
Access level
Specifies the access level required to be able to display and change the relevant
parameter. The required access level can be set via p0003.
The system uses the following access levels:
1. Standard
2. Advanced
3. Expert
4. Service
Please contact your local Siemens office for the password for parameters with
access level 4 (Service).
5. Macro (the parameter can only be changed via macro)
Note:
For p3900 > 0, also p0340 = 1 is automatically called.
After p1910 = 1, p0340 = 3 is automatically called.
Note:
Parameter p0003 is CU-specific (belongs to Control Unit).