Parameters
Overview of parameters
1-14
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
BICO: Full parameter name / Abbreviated name
The following abbreviations can be placed in front of the parameter name:
Drive object (function module)
A drive object (DO) is an independent, "self-contained" functional unit which pos-
sesses its own parameters and, in some cases, faults and alarms.
When carrying out commissioning using the commissioning software, you can
select/deselect additional functions and their parameters by activating/deactivat-
ing function modules accordingly.
The parameter list specifies the associated drive object and function module for
each individual parameter.
Note:
The parameter list can contain parameters that are not visible in the expert lists
of the particular commissioning software (e.g. parameters for trace functions).
BI: Binector input
This parameter is used for selecting the source of a digital signal.
BO: Binector output
This parameter is available as a digital signal for interconnection
with other parameters.
CI: Connector input
This parameter is used for selecting the source of an analog signal.
CO: Connector output
This parameter is available as an "analog" signal for interconnec-
tion with other parameters.
CO/BO: Connector/Binector Output
This parameter is available as an "analog" and digital signal for
interconnection with other parameters.
Note:
A connector input (CI) cannot be just interconnected with any connector output
(CO, signal source).
When interconnecting a connector input using the commissioning software, only
the corresponding possible signal sources are listed.
Note:
References: /FH1/ SINAMICS S120 Function Manual Drive Functions